Commonly used test standards for building materials exported to the European Union - EN13501-1 Determination of the combustion rating of building products and

Time: Author: SKYLINE Editor

I. EN 13501-1 Determination of fire classification of construction products and building elements - Name of standard:

EN 13501-1:2018:Fire classification of construction products and building elements-Part 1: Classification using data from reaction to fire tests

ü EN 13501-1:2018:Fire classification of construction products and building elements-Part 1: Classification using data from reaction to fire tests

ü EN 13501-1 Determination of the fire rating of building products and components - Overview of the standard:


With the fire science and fire engineering disciplines in the field of research and development, the connotation of combustion characteristics from the simple flame propagation and spread, extended to include combustion heat release rate, heat release, combustion smoke density and combustion product toxicity and other parameters. The classification system of EN 13501-1 is more scientific as it actively considers the above parameters. At the same time, EN 13501-1 stipulates some test methods that take into account both actual fire scenarios and the end-use of the material, and thus are more representative of the actual situation.


III. EN 13501-1 Fire classification of building products and components -- Classification:

Construction excluding Flooring / Construction products excluding flooring materials and linear piping

Classification:

a1,a2, b,c,d,e,f

Class F: Tested according to EN ISO 11925-2 but failing to meet the requirements of Class E.

Class E: Tested according to EN ISO 11925-2 and complies with the requirements.

Class D,C,B: Tested according to EN ISO 11925-2 and EN 13823 and comply with the requirements.

Class A2: Tested and conformed according to EN 13823 and ISO 1182 or ISO

1716.

Class A1: Tested according to EN ISO 1182 and EN ISO 1716 and comply with the requirements.

Class F: Tested according to EN ISO 11925-2 but failing to meet the requirements of Class E.

Class E: Tested according to EN ISO 11925-2 and complies with the requirements.

Class D,C,B: Tested according to EN ISO 11925-2 and EN 13823 and comply with the requirements.

Class A2: Tested and conformed according to EN 13823 and ISO 1182 or ISO

1716.

Class A1: Tested according to EN ISO 1182 and EN ISO 1716 and comply with the requirements.

Class Ffl: Tested according to EN ISO 11925-2 but failing to meet the requirements of Class Efl

Class Efl: Tested according to EN ISO 11925-2 and meets the requirements.

Class Dfl, Cfl, Bfl: Tested according to EN ISO 11925-2 and ISO 9239-1 and meets the requirements.

Class A2fl: according to ISO 9239-1 and ISO 1182 or ISO 1176.

Class A1fl: Tested according to EN ISO 1182 and EN ISO 1716 and conforms to the requirements.

Linear pipe / Linear pipe fittings

Classification:

a1l, a2l,bl,cl,dl,el,fl

Class FL: Tested according to EN ISO 11925-2 but failing to meet Class E requirements.

Class EL: Tested according to EN ISO 11925-2 and meets the requirements.

Class DL,CL,BL: Tested according to EN ISO 11925-2 and EN 13823 and meets the requirements.

Class A2L: Tested according to EN 13823 and ISO 1182 or ISO 1716.

1716

Class A1L: Tested according to EN ISO 1182 and EN ISO 1716 and comply with the requirements.








































IV. EN 13501-1 fire classification of building products and components - specific material application range

1. Sound and thermal insulation materials (mineral wool boards, glass wool, plastic parts, etc.)

2 textiles (curtains, etc.)

3 Floor coverings (bamboo flooring, wood flooring, plastic flooring, carpet, rubber flooring, WPC, SPC, etc.)

4 Pipe fittings (air-conditioning pipes, etc.)

5 wall panels, etc.



V. EN 13501-1 Fire classification of building products and components-Relevant reference standards

1 EN 13823: Fire test for building products, single unit combustion under thermal shock for building products (flooring materials)

 SKYLINE 's Single Burning Item can perform this test, please refer to the website 

2 EN ISO 1182: Fire test to building products, non-combustibility test

 SKYLINE 's Non Combustibility Test Furnace can perform this test

3 EN ISO 1716: Fire test to building products, Determination of calorific value of combustion

 Oxygen Bomb Calorimeter

4 EN ISO 9239-1: Fire test to flooring materials, Part 1: Determination of burning behaviour using radiant heat sources

Radiant Flooring Panel Apparatus SL-FL05

5 EN ISO 11925-2: Flame tests. Flammability of building products subjected to flame . Part II: Tests with a single source of ignition

ISO 11925-2 Building Material Flammability Tester SL-FL15


VI EN 13501-1 Fire classification of building products and elements - Tests to related similar standards

1 GB8624-2006: Classification of burning behaviour of building materials and products

2 DIN 4102-1: Fire behaviour of building materials and components Part I: Classification levels for requirements and testing of building materials

3 NF P 92-501: Fire test for building materials - M-burn determination

4 BS 476-7: Fire test to building materials - Surface burning